Battery state of health (SOH) describes how an aged battery compares with a defined beginning-of-life reference. It is usually shown as a percentage, but that percentage is not universal: one system may report remaining capacity, another may emphasize resistance or power capability, and a third may combine several indicators in a model.
Quick answer: Capacity-based SOH is commonly estimated as present measured capacity divided by a beginning-of-life reference capacity, multiplied by 100%. A battery that delivers 86 Ah under the same controlled protocol used for a 100 Ah reference has an 86% capacity-based SOH. That result does not automatically describe power capability, safety, remaining life, or performance at a different temperature or discharge rate.
This guide is educational. Capacity, pulse, and impedance tests can involve hazardous energy and must follow the exact battery, test-equipment, and site procedures. Do not improvise a live-pack test from a general article.
What Does Battery State of Health Mean?
SOH is a comparative indicator. It asks how a battery performs now relative to a stated reference, usually when the battery was new or after a defined commissioning period. The measured quantity and the reference must describe the same battery boundary and test conditions.
Capacity is the most familiar basis because it represents charge storage. The 2024 open-access review by Su and colleagues identifies capacity, resistance, and energy as common SOH indices and notes that definitions become more complicated when moving from cells to modules and packs. Cell inconsistency, topology, balancing, and operating limits can all affect the pack-level result (Wiley review).
SOH is therefore not a physical quantity that one sensor reads directly. Voltage, current, temperature, time, and sometimes impedance are measured; an algorithm or test protocol interprets those observations against a reference.
SOH Is Not the Same as SOC, SOP, or Remaining Life
Four battery terms answer different questions:
| Term | Question it answers | Typical output | Main limitation |
|---|---|---|---|
| State of charge (SOC) | How full is the battery now? | Percentage of available charge | A worn battery can still show 100% SOC |
| State of health (SOH) | How has a selected health metric changed from its reference? | Percentage or indexed value | The definition and method vary |
| State of power (SOP) | How much charge or discharge power is available now? | kW, A, or percentage | Depends on SOC, temperature, voltage limits, resistance, and cooling |
| Remaining useful life (RUL) | How long until a defined end condition is expected? | Cycles, time, or probability range | Requires a forecast, duty assumptions, and an end-of-life rule |
A health display should not be read as a countdown. An 86% SOH does not mean that exactly 14% of calendar life has been used or that 86% of service time remains. Battery aging can be nonlinear, and future temperature, storage state, cycle depth, current, and operating limits may differ from past use.
For the control-system context, see how a battery management system estimates states and applies limits.
The SOH Percentage Depends on Its Definition
Capacity-based SOH
The simplest capacity definition is:
SOHcapacity = measured available capacity / reference capacity × 100%
Capacity may be expressed in amp-hours. Energy-based health uses watt-hours instead, which incorporates the voltage delivered over the test. The two results can differ because voltage behavior also changes with load, temperature, cutoff settings, and aging.
The reference deserves attention. “Nominal capacity,” “rated capacity,” “initial measured capacity,” and “commissioning capacity” are not always identical. A useful report states which denominator it used and why.
Resistance- or impedance-based health
As a battery ages, some forms of resistance or impedance may change and reduce voltage support or power capability. However, there is no universal conversion from a resistance reading to remaining capacity. National Renewable Energy Laboratory research comparing capacity with DC resistance found that one resistance value could correspond to more than one capacity value across cell life, and that the relationship depended on the measurement time window (NREL paper).
Resistance is also sensitive to state of charge, temperature, recent operation, stimulus, sample time, and measurement boundary. The guide to battery internal resistance explains why DCIR, single-frequency AC resistance, and electrochemical impedance spectroscopy are not interchangeable numbers.
Composite or application-specific SOH
A BMS may combine capacity, resistance, voltage-curve features, temperature history, charge throughput, calendar time, imbalance, and fault data. Such a model can be useful, but its displayed percentage is meaningful only within the model’s definition, training or validation population, sensor accuracy, and operating range.

How Is Battery State of Health Estimated?
Controlled capacity or energy testing
A controlled test charges, rests, and discharges a battery according to a specified protocol while integrating current or energy until a defined endpoint. It produces a direct capacity or energy result for those conditions. This is conceptually strong but can take hours, remove equipment from service, consume energy, and require specialized safety controls.
Changing the temperature, rate, rest period, charge endpoint, discharge cutoff, or auxiliary loads changes the result. A field test should therefore be compared with the applicable manufacturer or commissioning protocol, not an unrelated laboratory example.
Resistance, pulse, or impedance diagnostics
These methods observe voltage response to a controlled current change or an AC excitation. They can support faster screening and trend analysis without a full discharge. Fluke’s maintenance guidance emphasizes that a single impedance measurement has little value without context and recommends building a consistent time-series baseline (Fluke).
The trade-off is interpretation. A fast resistance screen measures a health indicator, not necessarily remaining capacity. Temperature and SOC must be controlled or compensated, and the same instrument method and sense points should be retained when trending.
Model-based estimation
Equivalent-circuit and electrochemical models infer internal parameters from operating data. Filters can update estimated capacity or resistance as new voltage, current, and temperature observations arrive. These methods can operate online, but model mismatch, sensor bias, insufficient excitation, and unobserved operating regions can increase uncertainty.
Data-driven and hybrid estimation
Data-driven methods learn relationships between measured features and reference health labels. Hybrid approaches combine physical models with statistical or machine-learning methods. Reviews group modern SOH methods into direct measurement, model-based, data-driven, and hybrid families, each with different data, computation, interpretability, and transferability limits (International Journal of Energy Research).
A low error on one laboratory dataset does not prove equal accuracy for another chemistry, cell format, pack topology, duty cycle, climate, sensor set, or aging path. Validation must match the intended application.
A Worked SOH Example—and What It Does Not Prove
Assume a battery had a documented beginning-of-life capacity of 100 Ah under a specified test at 25°C. Later, the same protocol measures 86 Ah:
SOHcapacity = 86 Ah / 100 Ah × 100% = 86%
Now assume its DC resistance was 2.0 mΩ at commissioning and 2.8 mΩ later under a matched pulse method:
Resistance increase = (2.8 − 2.0) / 2.0 × 100% = 40%
These are two valid observations, but they are not two versions of the same percentage. Calling the second result “60% SOH” would require a validated application-specific transformation. The capacity result describes stored charge under the test protocol; the resistance trend describes a change related to voltage response and power behavior under its protocol.
Before accepting any health report, use this four-part check:
| Check | What the report should state | Why it matters |
|---|---|---|
| Definition | Capacity, energy, resistance, power, or composite SOH | Establishes what the percentage means |
| Reference | Rated, initial measured, commissioned, or model baseline | Defines the denominator |
| Conditions | Battery boundary, SOC, temperature, rate, endpoints, rest, and method | Determines comparability |
| Uncertainty | Repeatability, sensor accuracy, model error, confidence range, or validation scope | Prevents false precision |
If one of these is missing, the number may still support monitoring, but it should not be used as a stand-alone acceptance, warranty, safety, or resale decision.

Why Two SOH Readings Can Disagree
Different references
A tool using design capacity may report a different value from a system using measured commissioning capacity. Neither is automatically wrong; they answer slightly different questions.
Temperature and state of charge
Cold conditions can temporarily increase resistance and reduce available capacity without representing the same change as irreversible aging. Monolithic Power Systems notes that temperature-dependent voltage and impedance dynamics must be considered in SOC and SOH estimation (MPS).
Battery boundary
A cell result does not capture every pack effect. A module or pack adds joints, busbars, fuses, contactors, wiring, thermal gradients, balancing, cell variation, and control limits. A healthy average can also hide one weak series cell that limits usable pack energy.
Estimator learning and recalibration
Some algorithms need sufficiently informative charge or discharge events to update capacity. A displayed value may remain stable, jump after a qualifying event, or change after firmware, sensor, cell, or module service. The update behavior should be documented rather than interpreted as smooth physical aging.
Measurement noise and rounding
A one-point change can be smaller than the combined effects of sensor error, repeatability, environmental variation, and display rounding. Trend confidence requires comparable observations and an uncertainty statement.
How to Use SOH Without Overclaiming
For maintenance, trend the same battery with the same definition and method under comparable conditions. Combine SOH with cell spread, temperature, fault logs, isolation status where applicable, and actual duty performance. Investigate abrupt changes, disagreement among indicators, or a unit that diverges from comparable peers.
For procurement or warranty review, request the SOH definition, reference, test procedure, estimator version, validation range, expected accuracy conditions, update logic, and end-of-life criterion. A generic “SOH available” feature is not enough.
For repurposing, a headline capacity percentage cannot establish suitability. The new application may require a different power profile, thermal environment, protection architecture, reliability target, or regulatory evidence. Cell-to-cell variation and fault history may matter as much as average capacity.
When moving from education to product comparison, use the Polinovel battery directory only as a starting point and request model-specific capacity, resistance, operating-condition, BMS, warranty, and validation documentation.
Common Battery Health Misinterpretations
- “100% charged means 100% healthy.” SOC describes present fullness; SOH describes change from a health reference.
- “SOH is measured directly.” Sensors provide inputs; a protocol or algorithm creates the health estimate.
- “Every 80% threshold means replacement.” End-of-life is application-, warranty-, model-, and safety-plan-specific. Do not import a generic threshold.
- “Resistance reveals capacity.” Resistance can support diagnosis, but the relationship is not universally one-to-one.
- “SOH predicts exact remaining life.” RUL requires a future-use model and a defined end condition; SOH is a present estimate.
- “Pack average proves every cell is healthy.” Averages can conceal cell variation and local faults.
Frequently Asked Questions
What is a good battery state of health percentage?
There is no universal good percentage. The answer depends on the SOH definition, application requirement, manufacturer or warranty criterion, test conditions, uncertainty, and whether power, energy, faults, or cell variation impose a different limit. Compare the result with the applicable model-level documentation and service decision.
Can a BMS accurately calculate SOH?
A BMS can estimate SOH when its sensors, model, calibration, data coverage, and validation match the battery and operating conditions. Accuracy is not guaranteed by the presence of a percentage display. Ask what quantity is estimated, how the reference is established, and where the claimed error was validated.
Does SOH ever increase?
A displayed estimate can rise after recalibration, temperature normalization, a more informative cycle, sensor correction, or model update. Small early-life capacity changes can also occur in test datasets. An increase does not mean aging reversed; inspect the method and uncertainty.
Is SOH enough to judge a used battery?
No. It is one input. Review the definition and test report together with fault history, physical condition, cell consistency, resistance or power capability, thermal behavior, protection and communications, provenance, and suitability for the intended application.
Conclusion
Battery state of health is useful when its meaning travels with the number. A capacity ratio, resistance trend, energy result, and composite BMS score can all describe health, but they are not interchangeable.
Use SOH as a structured estimate: name the metric, identify the reference, match the conditions, and state the uncertainty. That approach turns a vague percentage into evidence that can support maintenance, comparison, and further testing—without pretending it proves safety or predicts an exact remaining lifetime.
Sources
- Su, X. et al. “State-of-Health Estimation of Lithium-Ion Batteries: A Comprehensive Literature Review From Cell to Pack Levels.” Energy Conversion and Economics, 2024. https://ietresearch.onlinelibrary.wiley.com/doi/10.1049/enc2.12125
- Gasper, P. et al. “Predicting Battery Capacity From Impedance at Varying Temperature and State of Charge Using Machine Learning.” Cell Reports Physical Science, 2022. https://www.nrel.gov/docs/fy23osti/82892.pdf
- Nuroldayeva, G. et al. “State of Health Estimation Methods for Lithium-Ion Batteries.” International Journal of Energy Research, 2023. https://onlinelibrary.wiley.com/doi/10.1155/2023/4297545
- Fluke. “Measuring Battery State of Health to Ensure Optimal Uptime.” Accessed September 2026. https://www.fluke.com/en/learn/blog/energy-efficiency/measuring-battery-state-of-health
- Monolithic Power Systems. “How Resistance, Temperature, and Charging Behaviors Impact Battery SOC and SOH.” December 13, 2023. https://media.monolithicpower.com/mps_cms_document/h/o/how-res-temp-and-charging-behavior-impact-soc-soh_r1.0.pdf